Hager RCD 25A Type A 30mA 2 Pole 2 Module CDA225U

Product Code CDA225U

reviews

Available for Delivery only, change to Fast Delivery Service

£24.49

exc VAT

£29.39 : inc VAT

£29.39

inc VAT

£24.49 : exc VAT

  • BULK SAVINGS!
  • QTY Unit Price
  • 1-2 £24.49 £29.39
  • 3+ £24.36 £29.23

Qty:

Hager CDA225U: 25A 30mA 2 Pole Type A RCCB (Residual Current Circuit Breaker) for DIN rail installation, providing automatic disconnection on earth fault conditions.

Safety & Reliability

This residual current circuit breaker RCCB opens the circuit automatically if it detects an earth fault between line and earth, or neutral and earth. The 30mA sensitivity and Type A leakage current rating mean it responds to both standard AC residual currents and pulsating DC faults, giving broader protection than a standard Type AC device on circuits feeding equipment with electronic components.

A trip-free mechanism is built in as standard, so the RCCB cannot be held closed against a genuine fault condition. It can also be padlocked in either the on or off position using a Hager MZN175 accessory, useful for isolation during maintenance or to prevent unauthorised reclosing.

Clear Status Indication

A rectangular flag indicator shows the switching state at a glance: red for closed, green for open, and yellow when the device has tripped on a fault. This means electricians and facilities staff can identify a tripped RCCB quickly on a busy distribution board without needing to test each way individually.

Installation & Compliance

Built to BS EN 61008 and IEC1008, this Hager RCCB is manufactured in France and suited to standard consumer unit and distribution board installations. Terminals accept 25mm² rigid or 16mm² flexible conductors, and the 2-module width keeps board layouts compact. DIN rail mounting and a 70mm recess depth make it straightforward to fit into most enclosures.

As a two-pole device rated at 25A with a 6kA short-circuit withstand rating, it is well suited to single-phase domestic and light commercial circuits where a dedicated residual circuit current breaker is needed ahead of final circuit protection.

Key Features of the Hager CDA225U RCCB Include:

  • Automatically Disconnects On Earth Fault Between Line/Neutral And Earth
  • Type A Leakage Current Detection Covers AC And Pulsating DC Faults
  • Trip-Free Mechanism Prevents Closing Onto A Live Fault
  • Can Be Padlocked On Or Off Using MZN175 Accessory
  • Flag Indicator Shows Closed (Red), Open (Green) And Tripped (Yellow) States
  • Compact 2-Module Width Suits Standard Distribution Boards
  • Rated Current: 25A
  • Rated Residual Operating Current: 30mA
  • Number Of Poles: 2
  • Rated Voltage: 230V
  • Rated Insulation Voltage (Ui): 500V
  • Rated Impulse Withstand Voltage (Uimp): 4kV
  • Short-Circuit Withstand Rating (Icw): 6kA
  • Surge Current Capacity: 0.25kA
  • Frequency: 50Hz
  • Ingress Protection Rating: IP20
  • Ambient Operating Temperature: -25°C And Above
  • Terminal Capacity: 25mm² Rigid / 16mm² Flexible
  • Mounting Method: DIN Rail
  • Recess Depth: 70mm
  • Width: 2 Modular Spacings
  • Compliance: BS EN 61008, IEC1008

If you need some help, would like to take advantage of our Price Promise or have a large order to place, give our team of professionals a call on 0203 994 5470, drop us an email at sales@electricpoint.com or use our Contact Form.

Model Number: CDA225U
Brand: Hager
Manufacturer: Hager Ltd
Product Type: Residual Current Circuit Breaker (RCCB)
Rated Current: 25A
Rated Residual Operating Current: 30mA
Leakage Current Type: Type A
Number Of Poles: 2
Rated Voltage: 230V
Rated Insulation Voltage (Ui): 500V
Rated Impulse Withstand Voltage (Uimp): 4kV
Short-Circuit Withstand Rating (Icw): 6kA
Surge Current Capacity: 0.25kA
Frequency: 50Hz
Pollution Degree: 2
Degree Of Protection: IP20
Mounting Method: DIN Rail
Width: 2 Modular Spacings
Recess Depth: 70mm
Connectable Conductor Cross Section (Solid-Core): 1mm²
Connectable Conductor Cross Section (Multi-Wired): 1mm²
Terminal Capacity (16-63A): 25mm² Rigid / 16mm² Flexible
Ambient Operating Temperature: -25°C And Above
Compliance: BS EN 61008, IEC1008
Trade Tariff Code: 85363030