Hager RCD 63A Type A 30mA 2 Pole 2 Module CDA263U

Product Code CDA263U

reviews

Available for Delivery only, change to Fast Delivery Service

£28.91

exc VAT

£34.69 : inc VAT

£34.69

inc VAT

£28.91 : exc VAT

  • BULK SAVINGS!
  • QTY Unit Price
  • 1-2 £28.91 £34.69
  • 3+ £28.75 £34.50

Qty:

Hager CDA263U: 63A 30mA 2 Pole RCCB Type A, a residual current circuit breaker designed to disconnect automatically in the event of an earth fault between line and earth or neutral and earth.

Safety & Reliability

As a Type A residual current circuit breaker (RCCB), this device detects both AC and pulsating DC earth leakage currents, giving broader protection than a standard AC-type unit. The trip-free mechanism ensures the breaker cannot be held closed against a fault, so protection is never compromised even under sustained pressure on the operating handle.

Clear Status Indication

A rectangular flag indicator shows red for closed and green for open, so installers and maintenance engineers can confirm switch position at a glance without opening the enclosure. A separate yellow flag indicates when the device has tripped on a fault, speeding up diagnosis on site.

Installation & Compliance

Terminals accept 25mm² rigid or 16mm² flexible conductors at this 63A rating, giving flexibility for a range of cable sizes on domestic and light commercial installations. The unit conforms to BS EN 61008 and IEC1008, supporting compliance sign-off without additional certification checks. DIN rail mounting across 2 modular spacings keeps consumer unit layouts compact.

Lockable for Safe Isolation

The RCCB can be padlocked in either the on or off position using a Hager Ltd MZN175 accessory, supporting safe isolation procedures during maintenance or fault-finding work. This is a straightforward way to prevent unauthorised re-energisation while work is in progress.

Key Features of the Hager CDA263U Include:

  • Automatically Disconnects On Earth Fault Between Line/Neutral And Earth
  • Type A Residual Current Circuit Breaker (RCCB), Detects AC And Pulsating DC Leakage
  • Trip-Free Mechanism Prevents Override During A Fault Condition
  • Flag Indicator: Red = Closed, Green = Open, Yellow = Tripped
  • Lockable Off Or On With Hager Ltd MZN175 Padlocking Accessory
  • Conforms To BS EN 61008 & IEC1008 For Straightforward Compliance
  • Rated Current: 63A
  • Rated Residual Current: 30mA
  • Number Of Poles: 2
  • Rated Voltage: 230V, Frequency: 50Hz
  • Rated Insulation Voltage (Ui): 500V, Rated Impulse Withstand (Uimp): 4kV
  • Short-Circuit Breaking Capacity (Icw): 6kA, Surge Current Capacity: 0.25kA
  • Terminal Capacity: 25mm² Rigid / 16mm² Flexible
  • Degree Of Protection: IP20, Pollution Degree 2
  • Operating Temperature: -25°C And Above
  • DIN Rail Mounting, 2 Modular Spacings Wide
  • Supplied As Single Unit (Order Quantity: 1)

If you need some help, would like to take advantage of our Price Promise or have a large order to place, give our team of professionals a call on 0203 994 5470, drop us an email at sales@electricpoint.com or use our Contact Form.

Model Number: CDA263U
Brand: Hager
Manufacturer: Hager Ltd
Product Type: Residual Current Circuit Breaker (RCCB)
Mounting Method: DIN Rail
Recess Depth: 70mm
Rated Current: 63A
Rated Voltage: 230V
Rated Insulation Voltage (Ui): 500V
Number Of Poles: 2
Rated Residual Current: 30mA
Leakage Current Type: Type A
Short-Circuit Breaking Capacity (Icw): 6kA
Surge Current Capacity: 0.25kA
Pollution Degree: 2
Width In Modular Spacings: 2
Frequency: 50Hz
Degree Of Protection (IP Rating): IP20
Connectable Conductor Cross Section (Solid-Core): 1mm² (Min)
Connectable Conductor Cross Section (Multi-Wired): 1mm² (Min)
Ambient Operating Temperature: -25°C And Above
Rated Impulse Withstand Voltage (Uimp): 4kV
Compliance: BS EN 61008, IEC1008
Order Unit: Each (Min Order Qty: 1)